Datasheet as PDF Three-phase transformers with cooling channels, three-phase power dry transformer, three-phase isolating transformers for high current
|
|
|
|
- 1 or 3 phases
- Vacuum varnished
- Power from 1 VA to 50 kVA
- Cheap and economical production due to several company locations
- Small transformers wound automatic
- Large transformers wound with a thick wire machine with 1700 mm width for the bobbin and automatic wire positioning
- More power due to optimisation via computer program
- Each transformer is calculated individually according to customer specification and standards
|
|
|
Field of application
|
|
Welding transformers, heating technology, testing transformers, resistance welding technology
|
|
Description
|
|
Three-phase transformers, built as high current transformers. The mounting must be done in a way that a convection through the cooling channels is possible. The block terminals are shock proof conform to VBG4. With our impregnation under vacuum the transformers have a very low hum-noise.
|
|
Technical data
|
|
Frequency: 50-60 Hz Natural cooling via air channels Winding without bobbin on GFK-profiles Temperatureclass B max. ambient temperature: 40°C Prepared for mounting upright with mounting angles Prepared for protection index I Impregnation with imbued lacquer Core grain oriented, low los metal sheets Fire class UL94V0 Quality management certificate ISO 9001
|
|
Type
|
Type size
|
Sec power
|
Current
|
Dimensions in [mm]
|
Mounting holes
|
Copper weight
|
Total weight
|
BV
|
b
|
l
|
h
|
f1
|
f2
|
f3
|
TEO
|
400/400/83 LK
|
20 kVA
|
3 x 800 A
|
505
|
290
|
480
|
183
|
430
|
15
|
50 kg
|
147 kg
|
-
|
TEO
|
400/400/83 LK
|
25 kVA
|
3 x 5000 A
|
505
|
290
|
480
|
183
|
430
|
15
|
80 kg
|
147 kg
|
3339002
|
TEO
|
400/400/140 LK
|
36 kVA
|
3 x 800 A
|
505
|
330
|
480
|
183
|
430
|
15
|
55 kg
|
160 kg
|
-
|
TEO
|
400/400/83 LK*
|
38 kVA
|
3 x 7500 A
|
505
|
290
|
480
|
183
|
430
|
15
|
80 kg
|
147 kg
|
3339002
|
TEO
|
500/500/150 LK
|
65 kVA
|
3 x 2500 A
|
600
|
252
|
570
|
-
|
-
|
-
|
124 kg
|
320 kg
|
-
|
TEO
|
600/600/200 LK
|
110 kVA
|
3 x 2500 A
|
720
|
330
|
680
|
-
|
-
|
-
|
167 kg
|
560 kg
|
-
|
TEO
|
700/700/200 LK
|
200 kVA
|
3 x 5740 A
|
840
|
440
|
750
|
-
|
-
|
-
|
372 kg
|
950 kg
|
-
|
TEO
|
800/800/200 LK
|
250 kVA
|
3 x 6014 A
|
950
|
550
|
850
|
-
|
-
|
-
|
530 kg
|
1250 kg
|
-
|
* with ventilation 2 m/s
|
Technical changes and optimisation reserved. All details are guide values, variations are possible.
|
07/2015
|
|
|
|