High potential isolating transformer up to 160 kV


Datasheet as PDF

 

ceenergysymb-schutzisoliertsymb-RoHssym-hv


High potential isolating transformers up to 160 kV separation


Table, sorted by isolating voltage


Type

Type size

Sec-
power

Isolating
voltage

Test
voltage

Dimensions in [mm]

Mounting holes

Copper
weight

Total
weight

BV

b

l

h

f1

f2

f3

TUVBWP

UI 310/300/50

2000 VA

60 kV

80 kV

570

320

727

295

535

11

35 kg

90 kg

-

TUVBWP

UI 260/240/50

2000 VA

80 kV

120 kV

450

260

359

225

415

11

-

-

1621993

HTT 3000-100

UI 310/300/50

500 VA

100 kV

-

570

330

727

295

535

Bolzen

35 kg

90 kg

-

HTT 3000-100

UI 310/300/50

1500 VA

100 kV

-

570

330

727

295

535

Bolzen

35 kg

55 kg

18018001

TUVBWP

UI 310/310/50

1000 VA

100 kV

120 kV

570

330

707

295

535

11

35 kg

90 kg

1509100a

TUVBWP

UI 310/310/50

2000 VA

100 kV

150 kV

570

330

727

295

535

11

35 kg

90 kg

16211139

TUVBWP

UI 360/360/50

3000 VA

150 kV

170 kV

630

400

727

-

-

-

50 kg

120 kg

3358000

TUVBWP

UI 310/310/50

1000 VA

150 kV

180 kV

570

330

727

295

535

11

35 kg

90 kg

13025008

TUVBWP

UI 400/400/60

5000 VA

150 kV

180 kV

680

430

727

395

645

11

30 kg

159 kg

32025000

TUVBWP

UI 310/300/50

2000 VA

160 kV

180 kV

570

320

727

285

535

11

35 kg

90 kg

2614004

Technical changes and optimisation reserved. All details are guide values, variations are possible.

01/2022


© 2022 Tauscher Transformatoren GmbH                                                                                                                                   Impressum / Privacy Policy